  data sheet the fc series ratio setter is used to set ratio for ratio control, and its set point signal is transmitted to a controller. this instrument uses a solid state indicator and a push- button operation system to provide reliable monitoring and operating functions. it also accepts a thermocouple, a resistance bulb and a 4 to 20ma dc input optionally. 1. high reliability this instrument is designed with few mechanical parts. it is mainly composed of electronic parts such as a solid state indicator which was formerly consisted of mechani- cal parts. 2. international standards this instrument is compact in size, conforming to inter- national standards iec. it operates on 24v dc power to deliver 1 to 5v dc signals as recommended by iec stand- ards. 100 and 200v ac power are also available for conven- ience of operation. 3. front panel operation process values and set points can be read accurately with digital indications on panel front. various parameter settings and setting operations are also possible from the front panel of the instrument. process value input (pv) square-root extraction linearize filter pv sv so alm kpv sv l r external set point input (cas or pi) (1 to 5v dc, pulse width, or pulse number) local mode output (ls) remote reque s (r-req) set point output (so) squared set point output (so2) high alarm output (h) low alarm output (l) ratio output signal (sv) compensated process value signal (kpv) remote acknowledge signal (r-ack) limiter r b1 b2 b3 h l limiter h l so 2 so = r x (sv+b 3 ) x (pv? 1 ) + b 2 png1 fc series ratio setter features functional diagram date EDS11-106E jul. 1, 1994
2 png1 1. ratio computing function computing formula ratio factor and ratio bias: setting range; ?27.6 to 327.67% computation cycle: 0.1 sec. (2) digital output signal: 5 points flt h l ls r-req fault output high alarm output low alarm output local mode output remote request open-collector output (photo- coupler insulation) output rating, 30v x 0.1a dc max. 4. indication, setting, operating functions (1) bargraph indication 2. input signal (1) process value input signal: one input selectable from the following input resistance, 1m ? or more 24v 2v dc can be supplied to transmitter in case of ac power supply approx. 35ma 10mv dc span or more cold junction compen- sation comprised 50 c span or more 1 to 5v dc 4 to 20ma dc type j: 0 to 600 c k: 0 to 1200 c e: 0 to 800 c r: 0 to 1600 c jpt100/pt100 ?0 to 500 c voltage in- put signal current in- put signal thermocou- ple input resistance bulb input allow. error 0.2%/fs* allow. error 0.2%/fs* allow. error 0.5%/fs* allow. error 0.5%/fs* i + i 0 i 3. output signal (1) analog output signal: 4 points compensated process value signal ratio output signal set point output squared set point output kpv sv so so2 1 to 5v dc output resistance, 1 ? or less allow. error 0.2%/fs pulse width input signal pulse number in- put signal on 0v, off 24v ( input current, approx. 11ma/24v dc) on 0v, off 24v ( approx. 11ma/24v dc), max. input frequency 500hz pl + pl contact input (photo-coupler insulation) (4) pulse width or pulse number input signal: 1 set (eithre one) (2) analog input signal: 1 point external set point cas 1 to 5v dc input resistance, 1m ? or more allow. error 0.2%/fs contact input (photo-coupler insulation) on 0v, off 24v ( input current, approx. 11ma/24v dc) remote acknowledge signal (3) digital input signal: 1 point r-ack note: *fs: full scale sv indicator led (green) pv indicator led (red) 101 + 2 0 to 100%, linear 1 %/fs 100mm so indicator led (red) 51 + 2 2%/fs 50mm 0 to 100% bargraph indication, 0 to 100% reverse bargraph indication, dot indication, ?0 to +50% deviation indication indication method no. of segments range resolution scale length indicating mode (2) operation mode indication indicating method: led (green) green: l, r (3) numerical value indication, setting indication method: led (red), name in 3 digits + numerical value in 5 digits (negative sign included) contents of indication: process value (industrial value), set point (industrial value), high/low alarm, etc. indication contents are selectable by f/s , , keys on front panel. setting method: by using f/s , , , , st keys on front panel (4) setting functions fixed value setting method: by using of , pushbuttons on front panel. setting speed, approx. 40 sec/fs remote setting method: by use of external set point signal (voltage or pulse input) tracking speed setting range; 0 to 900 sec/fs (5) operation mode changeover by using of r/l pushbutton on front panel. r l changeover r l changeover voltage signal* pulse width signal note: * balanceless bumpless by setting tracking speed balanceless bumpless balance bumpless balanceless bumpless 5 . power failure processing function power failure detection: setting output held at power failure detec- tion. during power failure: operating parameters backed up by capacitor up to 5 minutes. initial value of set point is stored in non-volatile memory (lasts 10 years expected at ambient temperature of 50 c or less). specifications so=r(sv+b3)(pv b1)+b2 computation output ratio factor ratio set point bias 3 process value bias 1 bias 2
3 power failure recovery: initial or continuous start mode can be set within 5 minutes of power failure. recovery from power failure lasting longer than 5 minutes is done by initial. note: ** control mode at initialzation can be registered l: local mode or r: remote mode 6. self-diagnosis functions computing circuit abnormality: flt lamp lights, flt contact output "on". manual operation output possible input/output signal abnormality: flt lamp lights, flt contact output "on", computation stops, operating output held fault contents indication: cause of fault is indicated numerically on numerical indicator on front panel 7. transmission functions (1) transmission items supervisory items: png host process value, set point, control output, operation mode, alarm information, fault information, various limiter values, constants, etc. setting operation items: host png set point, control output, operation mode, various limiter values, constants, etc. (2) transmission setting inhibit: parameter setting enable/inhibit can be designated by transmission from the host. designation is done by keys on the front panel. (3) communication interface (a) t-link: private interface transmission speed: 500kbps no. of units connectable: 32 max. transmission distance: 1km max. transmission form: multi-drop control method: i/o transmission and message (b) rs-422a/485: universal interface transmission speed: 2400, 4800, 9600 or 19200bps configurable no. of units connectable: 31 max. transmission distance: 1km max. transmission form: multi-drop control method: polling/selecting (c) cc data line: private interface transmission speed: 19.2kbps (fixed) no. of units connectable: 15 max. transmission distance: 500m max. transmission form: multi-drop control method: polling/selecting 8. other functions data protective function by pass code 9. operating conditions power supply: select from 3 types 24v dc (20 to 30v dc) 100v ac (85 to 132/47 to 63hz ac) 200v ac (187 to 264v/47 to 63hz ac) power consumption: approx. 11w (dc) approx. 20va (ac) dielectric strength: 1500v ac, 1 min. insulation resistance: 500v dc, 100m ? or more ambient temperature: 0 to 50 c ambient humidity: 90% rh or less enclosure: steel case rating plate (name plate): 100 (h) x 70 (w) mm, white acryl dimensions: 144 (h) x 72 (w) x 391 (d) mm, iec (din) standard mass {weight}: approx. 2.9kg mounting method: flush with indoor mounting; vertical mounting. mountable on tilted surface, angle " " finish color: munsell n 1.5 for both front panel and case scope of delivery: setter and mounting bracket item to be ordered separately: communication cable (type pnz) note: symbols for resistance bulb are as follows. jpt100.....jis c 1604-1981 pt100.....iec pub 751-1983 (selection of jpt100/pt100 possible by front key operation) code symbols =0 to 90 12345678 9 0 10 png1 a b c d e f g w a b 1 2 3 y t r s c 5 - description process value input signal 1 to 5v dc 4 to 20ma dc j thermocouple k thermocouple e thermocouple r thermocouple resistance bulb, jpt 100, 3-wire, 50 c span or more resitance bulb, pt100, 3-wire, 50 c span or more 10mv dc span or more, with cold junction compen- sation setting method l type r-l type power supply 24v dc (20 to 30v dc) 100v ac (85 to 132v/47 to 63hz ac) 200v ac (187 to 264v/47 to 63hz ac) transmission function none t-link rs-422a rs-485 cc data line
4 png1 terminal cover terminal panel thickness 8mm or less 140 16 support bracket 200min. when mounting 1 unit when mounting "n" units 355 36 mounting bracket 144 72 panel cutout 250min. (72.2n 4) +1 0 138 +1 0 no. of units n 2 200min. 138 +1 0 68 +0.7 0 outline diagram (unit:mm)
5 connections for process value input terminal block block terminals (m4 screw) kpv sv so so2 sc h l pc* pcd g note: * symbols for ac instrument power are vpo, pco, approx. 24v dc (0.1a max.) output. 51 52 53 54 55 56 57 58 59 60 61 62 71 72 73 74 75 76 77 78 79 80 81 82 cas sc r-req r-ack vp* vpd earth ai (external set point) ai, ao common bus do (remote request) di (remote acknowledge) instrument power (24v dc power, ac power) 24v power for di, do + + ao (compensated process value signal) ao (set ratio output signal) ao (set point output) ao (squared set point output) ai, ao common bus do (high alarm) do (low alarm) instrument power (24v dc, ac power) 24v power for di, do process value input do (local mode) i+ (pv) do (flt output) instrument power (ac) 11 i (sc) 12 ls 13 14 15 ac flt i o ac 16 31 32 33 34 35 (pulse width input or pulse number input) pi + pi 1 to 5v dc the 5th digit of code symbols a 4 to 20ma dc the 5th digit of code symbols b thermocouple the 5th digit of code symbols c,d,e,f resistance bulb the 5th digit of code symbols g,w 4 to 20ma dc with inner dc power supply of cc-s the 5th digit of code symbols b 11 + 31 12 11 12 11 12 11 12 11 12 31 31 60 pc 31 31 + + + + + + + connection diagram
communication connector 6 7 8 9 1 2 3 4 5 sig gnd shld(sd) inh txd+(t1) txd (t2) rxd + green red yellow brown black white rxd 6 7 8 9 1 2 3 4 5 sig gnd shld(sd) inh txd+(t1) txd (t2) rxd + rxd 6 7 8 9 1 2 3 4 5 shld(sd) sig gnd inh txd+(t1) txd (t2) rxd + green red yellow brown black host master controller white rxd 6 7 8 9 1 2 3 4 5 shld(sd) sig gnd inh txd+(t1) txd (t2) rxd + line termination registor rxd png1 png1 png1 png1 host communication cable termination resistor end station first station symbol in ( ): t-link terminal symbol note: png1 information in this catalog is subject to change without notice. printed in japan head office 6-17, sanbancho, chiyoda-ku, tokyo 102-0075, japan http://www.fesys.co.jp/eng sales div. international sales dept. no.1, fuji-machi, hino-city, tokyo, 191-8502 japan phone: 81-42-585-6201, 6202 fax: 81-42-585-6187 http: //www.fic-net.jp/eng caution on safety *before using this product, be sure to read its instruction manual in advance.


▲Up To Search▲   

 
Price & Availability of EDS11-106E

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X